Loom Motor Power Factor Correction Capacitor Calculator

The penalty is the visible saving. The transformer capacity you get back is often the larger one.

Load Present state
kW
cos φ
cos φ
Tariff Penalty
cos φ
% of bill
/month

Capacitor Bank Required

— kvar

To move from existing to target power factor

Correction Benefit

Apparent Power Before
— kVA
Apparent Power After
— kVA
Capacity Released
— kVA
Current Reduction
— %
Monthly Penalty Avoided
— /month
Annual Penalty Avoided
— /yr

Correcting to unity is the wrong target and a genuine hazard: a lightly loaded system with fixed capacitors can go leading, which some tariffs penalise as heavily as lagging and which can excite resonance with supply inductance. Target 0.95 to 0.97 and use automatic switched stages so correction follows load. **Capacitors and harmonics interact badly** — in a plant with significant drive harmonics, plain capacitors can form a resonant circuit with the supply and amplify distortion rather than help, so detuned reactors are usually mandatory alongside them. Size and specify with a measured load and harmonic survey by a qualified electrical engineer.

Loom Motor Power Factor Correction Capacitor Calculator — free, with the formula and a worked example, at Textile School.