Mill Utilities

Power Factor Correction kVAr Sizing, Demand Saving & Payback

Correction removes no kilowatts. It removes the kVA the tariff bills you for.

Load & Power Factor Where the plant is and where it should be
kW
Tariff & Cost What the correction is worth
/kVA/month
%
h/month
/kWh
/kVAr

Capacitor Bank Required

— kVAr

From the tangent difference at the stated active load

Apparent Power, Losses & Payback

Payback
— months
Apparent Power Removed
— kVA
Distribution Loss Reduction
— %
Present Apparent Power
— kVA
Corrected Apparent Power
— kVA
Demand Charge Saved
— /month
Penalty Avoided
— /month
Annual Saving
—

The calculation assumes a single representative operating point. Real plant load varies through the shift and across the week, so a bank sized from a peak reading over-corrects at light load - use automatic switched stages and size each from a load profile rather than a single measurement. Harmonic distortion is not modelled and is the main practical risk in a mill with many variable frequency drives: a plain bank can amplify harmonics or resonate with the supply, and a detuned bank costs more per kVAr than the figure entered here. The loss reduction applies only to the distribution between the metering point and the load, not to losses inside the motors. Tariff structures vary widely; confirm whether the charge is on peak kVA, on kVArh, or as an energy surcharge before trusting the saving.

Power Factor Correction kVAr Sizing, Demand Saving & Payback — free, with the formula and a worked example, at Textile School.